Page 21 - Catalog
P. 21
NITROTEL PRODUCT INFORMATION STRUCTURED CABLING STRUCTURED CABLING NITROTEL PRODUCT INFORMATION & PATCH CABLE LAN CABLE
STRUCTURED CABLING STRUCTURED CABLING
PATCH CORD PATCH CORD
U/UTP unshielded twisted airs ategory E F/UTP shielded twisted airs ategory E FACE PLATE
E
y
sli at h ord sli at h ord
PET
Copper Conductor Copper Conductor
HDPE Insulation HDPE Insulation MODULES
Pair Aluminum Foil
Jacket Jacket
Drain Wire
Standard Standard
Electrical performance guaranteed to meet or exceed Electrical performance guaranteed to meet or exceed
ANSI/TIA-568.2-D Category 5e and ISO/EIC specifications. ANSI/TIA-568.2-D Category 5e and ISO/EIC specifications.
Independently tested and verified UL. Independently tested and verified UL.
Ideal for Data center architectural requirements. Ideal for Data center architectural requirements.
Stranded cable for maximum flexibility. Stranded cable for maximum flexibility.
Available with different plug mold. Available with different plug mold.
Available with different color of cable. Available with different color of cable. PATCH PANELS
Available with different length. Available with different length.
Conductor Conductor
Conductor stranded bare copper 28AWG Conductor stranded bare copper 28AWG
Insulation HDPE rder in ormation ( art N m er Insulation HDPE rder in ormation ( art N m er
Total number of 8, twisted in 4 pairs NTPC5E_ _ _ _ SL Total number of NTPC5E_ _ _ _ FTPSL
insulated conductors insulated conductors 8, twisted in 4 pairs
White-Blue/Blue,White-Orange/Orange
White-Blue/Blue,White-Orange/Orange
Color code White-Green/Green,White-Brown/Brown Available Length Jacket Color Color code White-Green/Green,White-Brown/Brown Available Length Jacket Color
Individual pair shield None 01 02 03 BU WH Individual pair shield 01 02 03 BU WH
RD
YL
RD
YL
Overall shield None None
05 07 10 05 07 10
BK
BK
Drain wire None 15 25 50 GY GN OR Overall shield Aluminum foil, providing 100% 15 25 50 GY GN OR
coverage, foil face out.
Special orders available upon request. Drain wire None Special orders available upon request.
Nominal Transmission Characteristics & XPON OPTICAL FIBER
Prop. Delay Insertion PS PS Nominal Transmission Characteristics
Res. Length Freq. NE T RL ACR-N ACR-F PS NE T
Delay Skew Loss ACR-N ACR-F
Ω Max. n s ns Prop. Delay Insertion PS PS
Res. Length Delay Skew Freq. Loss NE T RL ACR-N ACR-F PS NE T ACR-N ACR-F
i 100m 555 50 1 3 60.0 17.0 57.0 57.4 57.0 54.0 54.4
4 4.5 53.5 17.0 49.1 45.4 50.5 46.1 42.4 Ω Max. n s ns
8 6.3 48.6 17.0 42.3 39.3 45.6 39.3 36.3 i 100m 555 50 1 3 60.0 17.0 57.0 57.4 57.0 54.0 54.4
10 7.1 47.0 17.0 39.9 37.4 44.0 36.9 34.4 4 4.5 53.5 17.0 49.1 45.4 50.5 46.1 42.4
16 9.1 43.6 17.0 34.5 33.3 40.6 31.5 30.3 8 6.3 48.6 17.0 42.3 39.3 45.6 39.3 36.3
20 10.2 42.0 17.0 31.8 31.4 39.0 28.8 28.4 10 7.1 47.0 17.0 39.9 37.4 44.0 36.9 34.4
25 11.4 40.3 16.0 28.9 29.4 37.3 25.9 26.4 16 9.1 43.6 17.0 34.5 33.3 40.6 31.5 30.3
31.25 12.9 38.7 15.1 25.9 27.5 35.7 22.9 24.5 20 10.2 42.0 17.0 31.8 31.4 39.0 28.8 28.4
62.5 18.6 33.6 12.1 15.0 21.2 30.6 12.0 18.5 25 11.4 40.3 16.0 28.9 29.4 37.3 25.9 26.4
100 24 30.1 10.0 6.1 17.4 27.1 3.1 14.4 31.25 12.9 38.7 15.1 25.9 27.5 35.7 22.9 24.5
62.5 18.6 33.6 12.1 15.0 21.2 30.6 12.0 18.5 CABINETS
100 24 30.1 10.0 6.1 17.4 27.1 3.1 14.4